TA_P Mini Split Core Transformers

Description: The mini split core TA_P current transformer for measurement instrumentation. Is a transformer for bus-bar primary and for cable of different dimensions. The casing is made of plastic and its main advantage is the easy of installation due to the possibility of openinng the core that clases with a clip. The mini transformer also hace the secondary cable included for easy of installation.

Connections

Dimensions

Model/ Bus-bar / Cable
TA10P / — / Ø10
TA16P / — / Ø16
TA24P / — / Ø24
TA36P / — / Ø36
TA50P / — / Ø52

• Bus-bar
• Split-core
• For cable plate
• Plastic envelope
• Easy installation

Security data

  • Continuous overload: 1,5 x In
  • Rated short-time therminal current: 60 x In
  • Rated dynamic current: 2,5 x Ith
  • Rated voltage (maximum): 750 V AC
  • Test voltage: 3 kV, 1 min
  • Frequency: 50-60 Hz

Additional information

  • Standard: EN 61869-2
  • Operating temperature: -15 ºC to +45 ºC
  • Storage temperature: -25 ºC to +75 ºC
  • Rated secondary current: /5A or /1A
  • Integral cable length: 1m

Standards

  • IEC 60185
  • UNE EN 618691 (IEC 618691)
  • UNE EN 618692 (IEC 618692)
  • VDE 0414
  • IEC60801-3.4
  • DIN 57414
  • BS 3938
  • EN 50081
  • EN 50082
  • IEC61010
  • UL94-V0

General technical specifications.

  • Security factor: Fs < 5
  • Rated voltage (maximum): 720 V
  • Test voltage: 3 kV AC (1min)
  • Frequency: 50 – 60 hz
  • Rated short-time thermal current: Ith limited by cable sizes or primary bus-bar
  • Rated dynamic current: IDyn = 2,5 x Ith
  • Continuous overload: ID = 1,2 x In
  • Operating temperature: -10 … 50 ºC
  • Accuracy: 0,5; 1 and 3 (0,2s; 0,5s on request)
  • Rated secondary current: /5 or /1A
  • Insulation class: Class E // Class B (130 ºC) Available

Details of product relationship table:

        

 

Solicitar información

TA_P Mini Split Core Transformers

Ask information

TA_P Mini Split Core Transformers