ATS1P, ATS2P Programmable Converters

The ATS2P converter measures resistance from an OLTC sensor, and the ATS1P converter measures temperature from a PT 100 or PT 1000 sensor. These devices convert the signal to a proportional and isolated DC current or voltage, measured from the circuit.

The converters are powered locally by a universal isolated power supply. These converters feature RS485 and USB communication ports, for configuration and data reading.

The ATS2P converter measures resistance from an OLTC sensor, and the ATS1P converter measures temperature from a PT 100 or PT 1000 sensor. These devices convert the signal to a proportional and isolated DC current or voltage, measured from the circuit.

The converters are powered locally by a universal isolated power supply. These converters feature RS485 and USB communication ports, for configuration and data reading.

ATS1PTemperature sensor PT-100

    • Temperature: PT100 probe (0-100; 0-600ºC)
    • Range: 0–100%
    • PT100 – PT1000

ATS2PResistance

    • Resistance: 0-100; 0-3000 Ohm
    • Range: 0–100%
    • OLTC Sensor


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Technical characteristics
    • Technical data

    ATS1PTemperature sensor PT-100

      • Temperature: PT100 probe (0-100; 0-600ºC)
      • Range: 0–100%
      • PT100 – PT1000

    ATS2PResistance

      • Resistance: 0-100; 0-3000 Ohm
      • Range: 0–100%
      • OLTC Sensor

    Communications

      • Serial port: RS485 / USB
      • Protocol: MODBUS/RTU
      • Communication speed: 2400, 4800, 9600 Bd

    ANALOGUE OUTPUT

    • Current: 4..20 mA / 0..5 mA
    • Voltage: 0..10 V
    • Load impedance: Ro (kΩ) = 12 / Io (mA) Max. (mA). Ro (kΩ) = Vo / 25 mA Min. (V)
    • Saturation limit: < 25 mA
    • Maximum open-circuit voltage: 16V

    Auxiliary power supply

    • Auxiliary voltage: Universal 40-270V AC/DC
    • Consumption: 1.37..2.2 VA. 0.63..1W
    • Frequency: 50 - 60 Hz