AQM2 - Power quality analyzer

The AQM2 power quality analyzer is designed for mass electrical data collection, offering an advanced solution for energy metering, remote power system monitoring and comprehensive power quality analysis thanks to its 0.2S accuracy class. With a memory capacity of 2 GB, the device allows the recording of events and waveforms. It also meets the requirements of EN 50160 and IEC61000-4-30 CL.A for network quality reporting.

The AQM2 network quality analyser is designed for bulk electrical data acquisition, offering an advanced solution for energy metering, remote control of the electrical system and comprehensive power quality analysis thanks to its 0.2S accuracy class.
With a memory capacity of 2 GB, the equipment allows for the logging of events and waveforms. It also meets the requirements of the EN 50160 standard and IEC61000-4-30 Class A for carrying out power quality reports.


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Connections
    • Dimensions
    • Technical characteristics
    • Technical data
    • Standards

    PARAMETER MEASUREMENT

    Power quality

    • Voltage deviation
    • Frequency deviation
    • Sequence components, imbalance
    • Harmonics
    • Interharmonics
    • Voltage flicker
    • Rapid changes in tension
    • Oscillation, voltage drop, voltage interruption
    • Peak factor
    • K-factor
    • Transient capture (80 μs)

    Memory 2 GB
    Energy measurement Class 0,2S
    TN, TT, IT networks

    VOLTAGE INPUT
    Rated voltage: 230/400V AC
    Continuous Overload: 1.2Vn,
    Inst. overload: 2Vn/1min
    Initial value: 10V
    Frequency: 45 - 65 Hz

    Standard EN50160
    Standard IEC61000-4-30 CL.A