TUC40-1 Current Transformers

The TUC40-1 is a current transformer for measurement, designed for electrical instrumentation applications in low-voltage installations. Its through-hole primary construction, compatible with cable or busbar, allows for simple installation, while its plastic casing provides a robust and reliable solution for electrical panels.

Compared to the standard TUC40 model, the TUC40-1 incorporates a larger core, allowing for greater precision at low transform ratios.

The TUC40-1 is a current transformer for measurement, designed for electrical instrumentation applications in low-voltage installations. Its through-hole primary construction, compatible with cable or busbar, allows for simple installation, while its plastic casing provides a robust and reliable solution for electrical panels.

Compared to the standard TUC40 model, the TUC40-1 incorporates a larger core, allowing for greater precision at low transform ratios.
tuc401
TUC40
tuc40_1


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Dimensions
    • Technical characteristics
    • Technical data
    • Standards
    • Ratios

    Model/ Bus-Bar/ Cable

    • TUC40-1 / 40×10 / Ø32
    • Window-type
    • For cable or busbar
    • Plastic enclosure
    • Wider profile
    • Getting more charging power
    • Application where instruments have the highest consumption.

     

    General technical data

    • Factor of safety: Fs < 5
    • Operating voltage (maximum): 720 V
    • Test voltage: 3 kV AC (1min)
    • Frequency: 50-60 hz
    • Rated thermal short-circuit current: 60 x In or Ith limited by the dimensions of the primary busbar or cable
    • Rated dynamic current: IDyn = 2,5 x Ith
    • Continuous overload: ID = 1.2 x In
    • Operating temperature: -5 / +40ºC
    • Accuracy: 0.5 -0.2s – 0.5s
    • Rated secondary current: x/5 or x/1A
    • Insulation class: Class E // Class B (130 ºC) available
    • IEC 60185
    • UNE EN 618691 (IEC 618691)
    • UNE EN 618692 (IEC 618692)
    • VDE 0414
    • IEC60801-3.4
    • DIN 57414
    • BS 3938
    • EN 50081
    • EN 50082
    • IEC61010
    • UL94-V0

    Details of the product ratio table: