Narrow Profile Transformers TU_PS
The TU__PS current transformer is used for measuring instrumentation. It is a transformer for through primary, either for cable or for plate and with different window sizes. Its enclosure is made of plastic and has a narrow profile, which allows a better adaptation in the panel due to its reduced dimensions. The TU_PS transformer has different transformation ratios, from 30A to 1000A. The accuracy is from 0.5 to 3 according to IEC 61869-2. This transformer is also available in special classes 0.5s, 0.2s and 0.2s.
Technical details
- Dimensions
- Technical characteristics
- Technical data
- Relations
Model/ Bar/ Cable
TU20PS/ 20×6/ Ø18
TU30PS / 30×10 / Ø25
TU40PS / 40×10 / Ø30
TU50PS / 50×10 / Ø40
TU60PS / 60×10 / Ø50
TU80PS / 80×30 / Ø70
TU100PS / 100×30 / -
TU125PS / 125×50 / -
For primary passant
For cable or plate
Plastic enclosure
Narrow profile
Standards
- IEC 60185
- UNE EN 618691 (IEC 618691)
- UNE EN 618692 (IEC 618692)
- VDE 0414
- IEC60801-3.4
- DIN 57414
- BS 3938
- EN 50081
- EN 50082
- IEC61010
- UL94-V0
General technical data
- Factor of safety: Fs < 5
- Operating voltage (maximum): 720 V
- Test voltage: 3 kV AC (1min)
- Frequency: 50-60 hz
- Rated thermal short-circuit current: Ith limited by cable or primary busbar dimensions
- Rated dynamic current: IDyn = 2,5 x Ith
- Continuous overload: ID = 1.2 x IN
- Operating temperature: -10 ... 50 ºC
- Accuracy: 0.5 - 1 - 3 (0.2s; 0.2 and 0.5s on request)
- Nominal secondary current: /5 or /1A
- Insulation class: Class E // Class B (130 ºC) available