Narrow Profile Transformers TU_PS

The TU__PS current transformer is used for measuring instrumentation. It is a transformer for through primary, either for cable or for plate and with different window sizes. Its enclosure is made of plastic and has a narrow profile, which allows a better adaptation in the panel due to its reduced dimensions. The TU_PS transformer has different transformation ratios, from 30A to 1000A. The accuracy is from 0.5 to 3 according to IEC 61869-2. This transformer is also available in special classes 0.5s, 0.2s and 0.2s.


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Dimensions
    • Technical characteristics
    • Technical data
    • Relations

    Model/ Bar/ Cable
    TU20PS/ 20×6/ Ø18
    TU30PS / 30×10 / Ø25
    TU40PS / 40×10 / Ø30
    TU50PS / 50×10 / Ø40
    TU60PS / 60×10 / Ø50
    TU80PS / 80×30 / Ø70
    TU100PS / 100×30 / -
    TU125PS / 125×50 / -

    For primary passant
    For cable or plate
    Plastic enclosure
    Narrow profile

    Standards

    • IEC 60185
    • UNE EN 618691 (IEC 618691)
    • UNE EN 618692 (IEC 618692)
    • VDE 0414
    • IEC60801-3.4
    • DIN 57414
    • BS 3938
    • EN 50081
    • EN 50082
    • IEC61010
    • UL94-V0

    General technical data

    • Factor of safety: Fs < 5
    • Operating voltage (maximum): 720 V
    • Test voltage: 3 kV AC (1min)
    • Frequency: 50-60 hz
    • Rated thermal short-circuit current: Ith limited by cable or primary busbar dimensions
    • Rated dynamic current: IDyn = 2,5 x Ith
    • Continuous overload: ID = 1.2 x IN
    • Operating temperature: -10 ... 50 ºC
    • Accuracy: 0.5 - 1 - 3 (0.2s; 0.2 and 0.5s on request)
    • Nominal secondary current: /5 or /1A
    • Insulation class: Class E // Class B (130 ºC) available

    Details of the product relationship table: