TPR_ Protection transformers
TPR__ protection transformers are through primary transformers, generally designed for cable, although they can also be manufactured for PCB (consult dimensions). These transformers are encapsulated in resin to make them more durable in electrical protection applications.
TPR__ protection transformers are through primary transformers, generally designed for cable, although they can also be manufactured for PCB (consult dimensions). These transformers are encapsulated in resin to make them more durable in electrical protection applications.
Technical details
- Dimensions
- Technical characteristics
- Technical data
- Ratios
Model/ / Cable
TPR60 / Ø60
TPR80 / Ø80
TPR100 / Ø100
TPR125 / Ø125
General technical data
- Safety factor: Fs < 5
- Operating voltage (maximum): 720 V
- Test voltage: 3 kV AC (1min)
- Frequency: 50-60 hz
- Rated short-circuit thermal withstand currentIth limited by the dimensions of the cable or the primary rod
- Rated dynamic current: IDyn = 2.5 x Ith
- Continuous overloadID = 1.2 x IN
- Operating temperature: -10 ... 50 ºC
- Accuracy: 0,5 - 1 - 3 (0,2s; 0,2 and 0,5s on request)
- Rated secondary current: /5 or /1A
- Insulation class:Class E // Class B (130 ºC) available
Standards
- IEC 60185
- UNE EN 61869-1 / -2 (IEC 61869-1 / -2 )
- VDE 0414
- IEC 60801/1-3.4
- DIN 57414
- BS 3938
- EN 50081
- EN 50082
- IEC 61010
- UL94-V0