TUC_ measuring transformers

TUC__ transformers for measuring instrumentation, with through primary, either for cable or for PCB. Their enclosure is made of plastic. TUC__ transformers have a transformation ratio for primary from 50A to 2500A and secondary in 1A or 5A. The accuracy can be 0.5, 1 and 3 according to IEC 61869-2.


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Dimensions
    • Technical characteristics
    • Technical data
    • Relations

    Model/ Bar/ Cable
    TUC30 / 30×10 / Ø25
    TUC40 / 40×10 / Ø32
    TUC50 / 50×10 / Ø40
    TUC60 / 60×10 / Ø51
    TUC80 / 80×30 / Ø65

    • Passing primary
    • For cable or busbar
    • Plastic enclosure
    • Wider profile
    • Getting more charging power
    • Application where instruments have the highest consumption.

    Standards

    • IEC 60185
    • UNE EN 618691 (IEC 618691)
    • UNE EN 618692 (IEC 618692)
    • VDE 0414
    • IEC60801-3.4
    • DIN 57414
    • BS 3938
    • EN 50081
    • EN 50082
    • IEC61010
    • UL94-V0

    General technical data

    • Factor of safety: Fs < 5
    • Operating voltage (maximum): 720 V
    • Test voltage: 3 kV AC (1min)
    • Frequency: 50-60 hz
    • Rated thermal short-circuit current: Ith limited by cable or primary busbar dimensions
    • Rated dynamic current: IDyn = 2,5 x Ith
    • Continuous overload: ID = 1.2 x IN
    • Operating temperature: -10 ... 50 ºC
    • Accuracy: 0.5 - 1 - 3 (0.2s; 0.2 and 0.5s on request)
    • Nominal secondary current: /5 or /1A
    • Insulation class: Class E // Class B (130 ºC) available