Instrument transformers. Narrow profile TU_R

The current transformer TU__R for measuring instrumentation. It is a transformer for through-plate primary. Its enclosure is made of resin, which gives it a special robustness and it has a narrow profile which allows a better adaptation in the panel due to its reduced dimensions.

Description: The current transformer TU__R for measuring instrumentation. It is a transformer for through-plate primary. Its enclosure is made of resin, which gives it a special robustness and it has a narrow profile which allows a better adaptation in the panel due to its reduced dimensions.


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Technical characteristics
    • Technical data
    • Ratios

    Model/ Bar/ Cable
    TU30R / 30×20 / Ø20
    TU60R / 60×30 / Ø30
    TU80R / 80×50 / Ø50
    TU100R / 100×80 / Ø80
    TU125R / 125×80 / Ø80
    TU160R / 160×80 / Ø80

    • Window-type
    • For plate
    • Resin enclosure
    • Special robustness
    • Narrow profile
    • Adaptation due to small dimensions

    Standards

    • IEC 60185
    • UNE EN 618691 (IEC 618691)
    • UNE EN 618692 (IEC 618692)
    • VDE 0414
    • IEC60801-3.4
    • DIN 57414
    • BS 3938
    • EN 50081
    • EN 50082
    • IEC61010
    • UL94-V0

    General technical data

    • Factor of safety: Fs < 5
    • Operating voltage (maximum): 720 V
    • Test voltage: 3 kV AC (1min)
    • Frequency: 50-60 hz
    • Rated thermal short-circuit current: Ith limited by cable or primary busbar dimensions
    • Rated dynamic current: IDyn = 2,5 x Ith
    • Continuous overload: ID = 1.2 x IN
    • Operating temperature: -10 ... 50 ºC
    • Accuracy: 0.5 - 1 - 3 (0.2s; 0.2 and 0.5s on request)
    • Nominal secondary current: /5 or /1A
    • Insulation class: Class E // Class B (130 ºC) available

    Details of the product ratio table: