Instrument transformers. Narrow profile TU_R
The current transformer TU__R for measuring instrumentation. It is a transformer for through-plate primary. Its enclosure is made of resin, which gives it a special robustness and it has a narrow profile which allows a better adaptation in the panel due to its reduced dimensions.
Description: The current transformer TU__R for measuring instrumentation. It is a transformer for through-plate primary. Its enclosure is made of resin, which gives it a special robustness and it has a narrow profile which allows a better adaptation in the panel due to its reduced dimensions.
Technical details
- Technical characteristics
- Technical data
- Ratios
Model/ Bar/ Cable
TU30R / 30×20 / Ø20
TU60R / 60×30 / Ø30
TU80R / 80×50 / Ø50
TU100R / 100×80 / Ø80
TU125R / 125×80 / Ø80
TU160R / 160×80 / Ø80
- Window-type
- For plate
- Resin enclosure
- Special robustness
- Narrow profile
- Adaptation due to small dimensions
Standards
- IEC 60185
- UNE EN 618691 (IEC 618691)
- UNE EN 618692 (IEC 618692)
- VDE 0414
- IEC60801-3.4
- DIN 57414
- BS 3938
- EN 50081
- EN 50082
- IEC61010
- UL94-V0
General technical data
- Factor of safety: Fs < 5
- Operating voltage (maximum): 720 V
- Test voltage: 3 kV AC (1min)
- Frequency: 50-60 hz
- Rated thermal short-circuit current: Ith limited by cable or primary busbar dimensions
- Rated dynamic current: IDyn = 2,5 x Ith
- Continuous overload: ID = 1.2 x IN
- Operating temperature: -10 ... 50 ºC
- Accuracy: 0.5 - 1 - 3 (0.2s; 0.2 and 0.5s on request)
- Nominal secondary current: /5 or /1A
- Insulation class: Class E // Class B (130 ºC) available