Low Voltage Supervisor SBT4V-5C

The team SBT4V-5C is a digital network analyser, the main purpose of which is to collect measurement information and data relating to a three-phase low-voltage network. It is capable of measuring the three main voltages and the three main currents of a three-phase installation. 


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Connections
    • Dimensions
    • Technical characteristics
    • Technical data
    • It is capable of measuring the voltages between phases L1, L2 and L3 with respect to the neutral and the voltage between the neutral and the protective earth.
    • 5 current measurement inputs that can be used for the measurement of the three main currents, L1, L2 and L3.
    • Auxiliary currents flowing in the neutral line and protective earth line
    • The equipment has several communication lines to be able to transmit data to remote systems where management and control tasks can be carried out.

    ELECTRICAL SPECIFICATIONS

    • Frequency: 50 - 60 Hz
    • Measuring range: 45 - 65 Hz
    • Voltage: 3 voltages and neutral
    • Phase-to-neutral measurement: 108 / 264 V AC
    • Measurement neutral-earth: 0 / 230 V AC
    • Current range: 1 / 5 A
    • Measuring range: 2 xIn
    • Power consumption: < 0.2 VA
    • Tickets: 5
    • Overcurrent: 20 xIn / 1 min
    • Auxiliary voltage: Self-powered
    • Range: 108 / 264 V AC phase-to-neutral
    • Power consumption: < 5W / 14 VA
    • Operating temperature: - 25 ºC / 70 ºC
    • Storage temperature: - 40 ºC / 85 ºC
    • Industrial frequency: 50 Hz, 2 kV
    • Temperature measurement: 3-wire PT 100
    • Temperature measurement range: - 50 ºC / 150 ºC

    ETHERNET COMMUNICATIONS

    • Connector: RJ 45
    • Isolation: Internal coupling transformer
    • Connection: Cat.5e cable
    • Speed: 10 / 100 automatic
    • Protocol: TCP Modbus
    • Port: 502

    RS232C / RS485 COMMUNICATIONS

    • Serial port: Optical isolation
    • Voltage: 2 kV / 1 min
    • Programmable baud rate: 1200 - 115200 bauds
    • Parity: Even, odd or none
    • Data bits: 5 - 8
    • Stop bits: 1 / 2
    • Protocol: Modbus RTU

    MECHANICAL SPECIFICATIONS

    • Material: Self-extinguishing plastic case UL94V0
    • Mounting: DIN rail
    • Connection: PT100 fixed terminal
    • Voltage terminals: 2.5 mm2
    • Current terminals: 4 mm2
    • Communications terminals: 1.5 mm2