TU_R Measuring transformers
Current transformer TU_R for primary winding. The resin enclosure makes the transformer more robust and makes it suitable for installation in adverse environments.
Current transformer TU_R for primary winding. The resin enclosure makes the transformer more robust and makes it suitable for installation in adverse environments.
TU3R
TU50R
measure
Technical details
- Dimensions
- Technical characteristics
- Technical data
- Ratios
- Standards
Models
TU3R
TU50R
- Factor of safety: Fs < 5
- Operating voltage (maximum): 720 V
- Test voltage: 3 kV AC (1min)
- Frequency: 50-60 hz
- Rated thermal short-circuit current: 60xIn or Ith limited by cable or primary busbar dimensions
- Rated dynamic current: IDyn = 2,5 x Ith
- Continuous overload: ID = 1.2 x In
- Operating temperature: -5 / + 40 ºC
- Accuracy: 0.5 - 1
- Rated secondary current: x/1 - x/5
- Insulation class: Class E // Class B (130 ºC) available
- IEC 60185
- IEC 61010
- UNE EN 61869-1 (IEC 61869-1)
- UNE EN 61869-2 (IEC 61869-2)
- UNE-EN 61000-6-3
- UNE-EN 61000-6-1
- UL94-V0
- VDE 0414
- DIN 57414
- BS 3938