Energy meter M1DL-MID

The energy meter M1DL-MID It is a single-phase direct measurement meter. It has MID Class B certification (EN50470-1 and EN 50470-3). The M1DL-MID meter has the approval certifying the correct reading of the consumed energy.

Description: The energy meter M1DL-MID It is a single-phase direct measurement meter. It has MID Class B certification (EN50470-1 and EN 50470-3). The M1DL-MID meter has the approval certifying the correct reading of the consumed energy.


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Connections
    • Dimensions
    • Technical characteristics
    • Technical data
    • Single-phase
    • MID Class B Certificate (EN 50470-1 and EN 50470-3)
    • Direct measurement up to 50 A
    • Internal shunt
    • LED power consumption indicator
    • 7-digit electronic counter
    • Pulse output: SO (DIN 43864)
    • 1 DIN module

    VOLTAGE INPUT

    • Rated voltage (Un): 230 V AC
    • Self consumption: < 8 VA, 2 W
    • Measuring range: ± 15% Un
    • Frequency: 50 Hz

    CURRENT INPUT

    • IB Intensity (IMAX): 0.25 to 5 (50) A
    • Own consumption: < 1 VA
    • Measurement range: 0 – 100% IMAX
    • Starting current (In): < 0,4% IB

    Output pulses 

    • Number of outlets: 1
    • Impulse weight: 1000 pulses / kWh
    • Type SO (DIN 43864): Optocoupler
    • Isolation: 3 kV, 1 min
    • Maximum current: 50 mA
    • Voltage: 5 – 48 V DC
    • Pulse duration: > 70 ms