TUP50PR Measurement Transformers

El TUP50PR is a current transformer of double secondary for measurement and protection applications. Available in versions of measure, protection or combined, enables both functions to be integrated into a single unit with secondary configurations of x/1 A – x/5 A, x/1 A – x/1 A, or x/5 A – x/5 A.

Its construction, encapsulated in resin and its through-primary design for cable or busbar, provides a robust and reliable solution for industrial and electrical distribution installations.

El TUP50PR is a current transformer of double secondary for measurement and protection applications. Available in versions of measure, protection or combined, enables both functions to be integrated into a single unit with secondary configurations of x/1 A – x/5 A, x/1 A – x/1 A, or x/5 A – x/5 A.

Its construction, encapsulated in resin and its through-primary design for cable or busbar, provides a robust and reliable solution for industrial and electrical distribution installations.

tup50pr-d


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Dimensions
    • Technical characteristics
    • Technical data
    • Standards
    • Ratios

    Model/ Bus-Bar/ Cable

    • TUP50PR 125x50 / Ø50
    • Window-type
    • For cable or busbar
    • Encapsulated in resin
    • Wider profile

    General technical data

    • Factor of safety: Fs < 5
    • Operating voltage (maximum): 720 V
    • Test voltage: 3 kV AC (1min)
    • Frequency: 50-60 hz
    • Rated thermal short-circuit current: 60 x In or Ith limited by the dimensions of the primary busbar or cable
    • Rated dynamic current: IDyn = 2,5 x Ith
    • Continuous overload: ID = 1.2 x In
    • Operating temperature: -5 / +40ºC
    • Accuracy: 0.5 – 1 – 3 (0.2s – 0.5s on request)
    • Rated secondary current: x/5 or x/1A
    • Insulation class: Class E // Class B (130 ºC) available
    • IEC 60185
    • UNE EN 618691 (IEC 618691)
    • UNE EN 618692 (IEC 618692)
    • VDE 0414
    • IEC60801-3.4
    • DIN 57414
    • BS 3938
    • EN 50081
    • EN 50082
    • IEC61010
    • UL94-V0