AC/DC programmable maximum ammeters
- Instantaneous, average and maximum current value.
- Average current value (adjustable time interval 8, 15, 20 and 30 Min).
- True eficient value.
- Keypad programmable alarm
‘Instantaneous, average and maximum current value.
- Average current value (adjustable time interval 8, 15, 20 and 30 Min).
- True eficient value.
- Keypad programmable alarm.
Technical details
- Technical characteristics
- Technical data
Model // Dimensions // Measuring range // Alarm on current type
DP46M // (72×36 mm) // x/1 A or x/5 A // Integrated
DP46MIR // (72×36 mm) // x/1 A or x/5 A // Instantaneous
DP46MII // (72×36 mm) // x/1 A or x/5 A // Inverted Snapshot
DP46MC // (72x36mm) // x/60 mV // Integrated
Display: Red LED, digit height 10.2 mm, high brightness.
Max reading: 9999
Overrange indication: F.ESC
Accuracy: 0,5% of the range ± 1 Digit
Temperature quotient: 0.01% / ºC
Alarm circuit: 1 potential-free contact (250 V, 3 A, 200 VA)
Auxiliary voltage: AC 110, 230 V± 20 % Own consumption < 3 VA
Auxiliary voltage: DC 12, 24, 48 or 110 V ± 20% Own consumption < 2 W