Low Voltage Supervisor SBT4V-5C
The team SBT4V-5C is a digital network analyser, the main purpose of which is to collect measurement information and data relating to a three-phase low-voltage network. It is capable of measuring the three main voltages and the three main currents of a three-phase installation.
Technical details
- Connections
- Dimensions
- Technical characteristics
- Technical data
- It is capable of measuring the voltages between phases L1, L2 and L3 with respect to the neutral and the voltage between the neutral and the protective earth.
- 5 current measurement inputs that can be used for the measurement of the three main currents, L1, L2 and L3.
- Auxiliary currents flowing in the neutral line and protective earth line
- The equipment has several communication lines to be able to transmit data to remote systems where management and control tasks can be carried out.
ELECTRICAL SPECIFICATIONS
- Frequency: 50 - 60 Hz
- Measuring range: 45 - 65 Hz
- Voltage: 3 voltages and neutral
- Phase-to-neutral measurement: 108 / 264 V AC
- Measurement neutral-earth: 0 / 230 V AC
- Current range: 1 / 5 A
- Measuring range: 2 xIn
- Power consumption: < 0.2 VA
- Tickets: 5
- Overcurrent: 20 xIn / 1 min
- Auxiliary voltage: Self-powered
- Range: 108 / 264 V AC phase-to-neutral
- Power consumption: < 5W / 14 VA
- Operating temperature: - 25 ºC / 70 ºC
- Storage temperature: - 40 ºC / 85 ºC
- Industrial frequency: 50 Hz, 2 kV
- Temperature measurement: 3-wire PT 100
- Temperature measurement range: - 50 ºC / 150 ºC
ETHERNET COMMUNICATIONS
- Connector: RJ 45
- Isolation: Internal coupling transformer
- Connection: Cat.5e cable
- Speed: 10 / 100 automatic
- Protocol: TCP Modbus
- Port: 502
RS232C / RS485 COMMUNICATIONS
- Serial port: Optical isolation
- Voltage: 2 kV / 1 min
- Programmable baud rate: 1200 - 115200 bauds
- Parity: Even, odd or none
- Data bits: 5 - 8
- Stop bits: 1 / 2
- Protocol: Modbus RTU
MECHANICAL SPECIFICATIONS
- Material: Self-extinguishing plastic case UL94V0
- Mounting: DIN rail
- Connection: PT100 fixed terminal
- Voltage terminals: 2.5 mm2
- Current terminals: 4 mm2
- Communications terminals: 1.5 mm2
- Protection: IP 40