TCIL2 Energy meter
The TCIL2 meter + analyser acts as an energy meter and measures the parameters of a three-phase or single-phase low-voltage network. It has RS 485 communication and the capacity to connect 32 devices on the same circuit or 128 via converter. Control can be done via computer or network from the device. It is also available with Ethernet port. Up to 6 electricity tariffs can be configured.
The TCIL2 meter + analyser acts as an energy meter and measures the parameters of a three-phase or single-phase low-voltage network. It has RS 485 communication and the capacity to connect 32 devices on the same circuit or 128 via converter. Control can be carried out via computer or network from the device.
Also available with Ethernet port. Up to 6 electricity tariffs can be configured.
ETIM Class: EC001506
TCIL2
TCIL2-TCP
TCIL2T
TCIL2T-TCP
TCIL2T-LP
TCIL2T-LP-TCP
065917
066023
065996
066025
066024
066026
Technical details
- Technical characteristics
- Technical data
- Standards
- Versions
- Connections
Meter with the ability to reset the active energy meter, as well as perform a partial reset of the data.
Modbus or Bacnet communications (programmable)
Measuring quantities:
- Consumption of a three-phase or single-phase network
- Current
- Voltage (Phase-Phase and Phase-Neutral)
- Frequency
- Power factor
- Energy (imported and exported). Measured in the 4 quadrants
- Active and reactive power (per phase and total)
- Power quality analysis (THD V and I, harmonics up to 31, max. demand I, P, Q, S)
ETIM Class: EC001506
VOLTAGE INPUT
- Rated voltage: 3 x 230 / 400 V AC
- Voltage measuring range: 63 to 276 Vpn AC
- Frequency: 50 - 60 Hz
- Network type: 1P2W, 3P3W and 3P4W
CURRENT INPUT
- Base current: 1.5 (6) A
- Rated current: /5 or /1 programmable
- Maximum current: 2 Inom
- Current measuring range: 0 - 120% Inom
- Starting current: 3 mA
- Maximum self-consumption: < 0.1 VA
- Continuous overload: 2 In
- Instantaneous overload: 30 In 1s
- Baud rate: 1200 - 19200 bps
- Refill material: ABS, UL94 V0
Auxiliary Voltage
- Auxiliary voltage: Self-powered
- Auxiliary voltage consumption: < 0.6 VA per phase
- EN 62053-21
- EN 62053-22
- EN 62053-23
- DIN 43864
- EN 61010