TUP_R Measuring transformers

The current transformer TUP__R for measuring instrumentation. It is a transformer for through primary, generally for PCBs. Its enclosure is made of resin, which makes it more robust and makes it suitable for installation in adverse environments.

Description: The current transformer TUP__R for measuring instrumentation. It is a transformer for through primary, generally for PCBs. Its enclosure is made of resin, which makes it more robust and makes it suitable for installation in adverse environments.


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Dimensions
    • Technical characteristics
    • Technical data
    • Ratios

    Model/ Bar/ Cable
    TUP20RC / 80×20 / Ø20
    TUP20R / 100×20 / Ø20
    TUP60R / 100×60 / Ø60
    TUP95R / 100×95 / Ø95

    • Window-type
    • For flat bars
    • Resin enclosure
    • Increased robustness
    • Possibility of installation in harsh environments

    Standards

    • IEC 60185
    • UNE EN 618691 (IEC 618691)
    • UNE EN 618692 (IEC 618692)
    • VDE 0414
    • IEC60801-3.4
    • DIN 57414
    • BS 3938
    • EN 50081
    • EN 50082
    • IEC61010
    • UL94-V0

    General technical data

    • Factor of safety: Fs < 5
    • Operating voltage (maximum): 720 V
    • Test voltage: 3 kV AC (1min)
    • Frequency: 50-60 hz
    • Rated thermal short-circuit current: Ith limited by cable or primary busbar dimensions
    • Rated dynamic current: IDyn = 2,5 x Ith
    • Continuous overload: ID = 1.2 x IN
    • Operating temperature: -10 ... 50 ºC
    • Accuracy: 0.5 - 1 - 3 (0.2s; 0.2 and 0.5s on request)
    • Nominal secondary current: /5 or /1A
    • Insulation class: Class E // Class B (130 ºC) available

    Details of the product ratio table: