TUP_R Protection transformers (homopolar)
Current transformers for the measurement of homopolar currents. They have a low transformation ratio and high sensitivity.
These large window-type transformers allow all 3 current phases to pass through the transformer core in order to detect current unbalance (or earth leakage currents if the neutral is included).
They are designed to accommodate several cables, but can also be used with busbars. They are encapsulated in resin.
Current transformers for the measurement of homopolar currents. They have a low transformation ratio and high sensitivity.
These large window-type transformers allow all 3 current phases to pass through the transformer core in order to detect current unbalance (or earth leakage currents if the neutral is included).
They are designed to accommodate several cables, but can also be used with busbars. They are encapsulated in resin.
Technical details
- Dimensions
- Technical characteristics
- Technical data
- Standards
- Ratios
Model/ Busbar
TUP310R / 310×80
TUP300R / 384×84
TUP900R / 905×145
Protection instrument
Window-type
Generally for busbar
Encapsulated in resin
General technical data
- Operating voltage (maximum): 720 V
- Test voltage: 3 kV AC (1min)
- Accuracy: 5P10
- Frequency: 50-60 hz
- Rated thermal short-circuit current: 60xIn or Ith limited by the dimensions of the primary busbar or cable
- Rated dynamic current: IDyn = 2,5 x Ith
- Continuous overload: ID = 1.2 x In
- Operating temperature: -5 / +40ºC
- Rated secondary current: X/1A
- Insulation class: Class E
- IEC 60185
- UNE EN 618691 (IEC 618691)
- UNE EN 618692 (IEC 618692)
- VDE 0414
- IEC60801-3.4
- DIN 57414
- BS 3938
- EN 50081
- EN 50082
- IEC61010
- UL94-V0
TUP310R: 60/1A. 0,25VA
TUP300R: 60/1A. 0,25VA
TUP900R: 60/1A. 0,25VA