TU_ Measuring transformers
Current transformers TU__ for measuring instrumentation, are designed for through-hole primary, either for cable or for PCB. Their enclosure is made of plastic.
Technical details
- Dimensions
- Technical characteristics
- Technical data
- Relations
Model / Bar / Cable
TU20 / 20×5 / Ø16
TU30 / 30×10 / Ø22
TU40 / 40×10 / Ø30
- Passing primary
- For cable or busbar
- Plastic enclosure
- Narrow profile
Standards
- IEC 60185
- UNE EN 618691 (IEC 618691)
- UNE EN 618692 (IEC 618692)
- VDE 0414
- IEC60801-3.4
- DIN 57414
- BS 3938
- EN 50081
- EN 50082
- IEC61010
- UL94-V0
General technical data
- Factor of safety: Fs < 5
- Operating voltage (maximum): 720 V
- Test voltage: 3 kV AC (1min)
- Frequency: 50-60 hz
- Rated thermal short-circuit current: Ith limited by cable or primary busbar dimensions
- Rated dynamic current: IDyn = 2,5 x Ith
- Continuous overload: ID = 1.2 x IN
- Operating temperature: -10 ... 50 ºC
- Accuracy: 0.5 - 1 - 3 (0.2s; 0.2 and 0.5s on request)
- Nominal secondary current: /5 or /1A
- Insulation class: Class E // Class B (130 ºC) available