TU_ Measuring transformers. Primary wound

TU_ current transformers for measurement applications. It is a transformer with primary wound and built-in horizontal bar or screw terminal connection.

The enclosure is made of plastic and can be resin-filled for installation in more hostile environments. Connections can be for cable or terminal block.

TU__ current transformers for measuring instrumentation. It is a transformer with primary winding for low currents. Its enclosure is made of plastic and can be filled with resin for installation in more hostile environments. The connections can be for cable or plate.


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Dimensions
    • Technical characteristics
    • Technical data
    • Ratios

    Horizontal bar

    Model  / Bar (mm)
    TU3BP / 4×25
    TU3BCP / 4×25
    TU3BAP / 4×25

    Screw terminal

    TU3AP
    TU40CP

    • Primary wound
    • For cable or busbar
    • Plastic enclosure
    • Available in resin
    • Narrow profile

    Standards

    • IEC 60185
    • UNE EN 618691 (IEC 618691)
    • UNE EN 618692 (IEC 618692)
    • VDE 0414
    • IEC60801-3.4
    • DIN 57414
    • BS 3938
    • EN 50081
    • EN 50082
    • IEC61010
    • UL94-V0

    General technical data

    • Factor of safety: Fs < 5
    • Operating voltage (maximum): 720 V
    • Test voltage: 3 kV AC (1min)
    • Frequency: 50-60 hz
    • Rated thermal short-circuit current: Ith = 60 In for primary winding.
    • Rated dynamic current: IDyn = 2,5 x Ith
    • Continuous overload: ID = 1.2 x IN
    • Operating temperature: -10 ... 50 ºC
    • Accuracy: 0.5 - 1 - 3 (0.2s; 0.2 and 0.5s on request)
    • Nominal secondary current: /5 or /1A
    • Insulation class: Class E // Class B (130 ºC) available

    Details of the product ratio table: