ATIP ATUP measurement converter

The measurement converter ATIP ATUP is controlled by a 16-bit microprocessor. Its configuration is carried out by means of software. It has 1 analogue output and USB and RS485 serial port. Universal power supply 40V to 275 AC/DC.

Description: The measurement converter ATIP ATUP is controlled by a 16-bit microprocessor. Its configuration is carried out by means of software. It has 1 analogue output and USB and RS485 serial port. Universal power supply 40V to 275 AC/DC.


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Connections
    • Transfer curves
    • Technical characteristics
    • Technical data

    ANALOGUE OUTPUTS

    • Software configurable, start, end of scale and over range supported. In case of ATUP, turning point for broken curve.
    • Isolated from measurement input, auxiliary voltage and RS485 port. No USB port

    CONFIGURATION

    • MODBUS ID
    • Baud rate, default, 9600 bauds
    • Primary current or primary voltage
    • Secondary current or voltage
    • Analogue output configuration

    PORT SERIES

    • USB and RS485. MODBUS/RTU protocol
    • RS 485 isolated from input voltage, auxiliary voltage and analogue output.
    • SB isolated from input voltage and auxiliary voltage. Not from the analogue output. Can be configured via USB without power supply.

    STANDARDS

    • IEC 60688 Electrical measuring transducers
    • IEC 61010 Safety requirements
    • IEC 61326 Electromagnetic Compatibility Requirements
    • UL 94 Flammability
    • IEC 60038 Standardised voltage and current values

    INPUT (SECONDARY)

    • ATIP: X/5 and X/1A
    • ATUP: 230V and 110V. On the 110V input, other secondary values can be programmed, 57, 7V; 63, 5 V; 100V;...
    • Measuring range: Up to 120%

    ANALOGUE OUTPUT

    • DC current : 4..20mA and 0...5mA. Other values on request
    • DC voltage: 0..10V. Other values on request
    • Load impedance : Ro (kΩ) = 12/Io (mA) Max. for mA / Ro (kΩ) =Vo / 30 mA min. for V
    • Saturation limit: 120%
    • Max. open-circuit voltage value: 16 V
    • ATIP: Curly ≤ 3 %
    • ATUP: Ripple ≤ 0,3 %
    • Response time: ≤ 200 ms (0 - 90 % lo)
    • AUXILIARY VOLTAGE
      40..275V AC/DC, Power consumption: 1, 37..2,2 VA. 0,63..1W