M1DL1 Energy meter

The energy meter M1DL1 is a single-phase, direct measurement meter up to 50 A. It has an accuracy of Cl.1 (EN 62053). It has an internal shunt. It has an LED energy consumption indicator.

Description: The energy meter M1DL1 is a single-phase, direct measurement meter up to 50 A. It has an accuracy of Cl.1 (EN 62053). It has an internal shunt. It has an LED energy consumption indicator.


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Connections
    • Dimensions
    • Technical characteristics
    • Technical data
    • Versions
    • Single-phase
    • Accuracy Cl.1 (EN 62053)
    • Direct measurement up to 50 A
    • Internal shunt
    • LED power consumption indicator
    • 7-digit electronic counter
    • Pulse output: SO (DIN 43864)
    • 1 DIN module

    Standards

    • EN 62053-21
    • EN 62053-22
    • EN 62053-23
    • DIN 43864
    • EN 61010

    VOLTAGE INPUT

    • Rated voltage (Un): 230 V AC
    • Self consumption: < 8 VA, 2 W
    • Measurement range: ± 15 % Un
    • Frequency: 50 - 60 Hz

    CURRENT INPUT

    • IB current (IMAX): 5 (50) A
    • Own consumption: < 1 VA
    • Measuring range: 0 - 100 % IMAX
    • Starting current (In): < 0,4% IB

    PULSE OUTPUT (OPTOCOUPLER)

    • Number of outlets: 1
    • Impulse weight: 1000 pulses / kWh
    • Type SO (DIN 43854): Optocoupler
    • Isolation: 3 kV, 1 min
    • Maximum current: 50 mA
    • Voltage: 5 - 48 V DC
    • Pulse duration: > 70 ms

    M1DL1-MID