TCIDL-MID Energy meter
The TCIDL-MID three-phase meter + analyser is designed not only to act as an energy meter, but also to measure three-phase network parameters such as voltage, current, active, reactive and apparent power, power factor, frequency and maximum demand at low voltage. It stands out for its RS-485 and infrared communication with the potential to connect up to 32 units in the same loop or 128 through a converter, being able to be controlled from any computer or network device.
The TCIDL-MID three-phase meter + analyser is designed not only to act as an energy meter, but also to measure three-phase network parameters such as voltage,
current, active, reactive and apparent power, power factor, frequency and maximum demand at low voltage.
It stands out for its RS-485 and infrared communication with the potential to connect up to 32 devices in the same loop or 128 through a converter, being able to be controlled from any computer or networked device.
Technical details
- Technical characteristics
- Technical data
- Standards
- Rated voltage: 3 x 230 / 400 V A.C.
- Measuring range voltage: 3×230 V ±30%
- Rated current: 0.25 - 5(80)A
- Current measuring range: 0-100 % IMAX
- Starting current (In): <0,4% IB
- Frequency:50-60 Hz
- Maximum self-consumption: < 10 VA; < 2 W
- Mounting type: DIN rail
- Display Type: LCD
- Resolution: 6 whole digits and 2 decimals
- Pulse outputs: Output type SO (DIN 43864)
- Communication port: RS485 / IR
- Type of terminals: Sealable
EN 62053 -21
EN 62053-22
EN 62053-23
DIN 43864
EN 61010
EN 50470-1
EN 50470-3
EN 62053-23
DIN 43864
EN 61010