TTI-TTIM Energy meter

Categories:
Description: The TTI-TTIM totalizer module has a microprocessor and serial output with 128 Kb memory and integrated LCD display and keypad.

Connections

Dimensions

  • 8 independent impulse counters
  • Independent counter reset
  • Programmable counter value
  • TTIM: 90 days of load curve per meter
  • RS485 serial output
  • Programmable (can count closed contact time in seconds, time or pulses)

ENTRANCE

Number of inputs: 8
Pulse duration: > 100 ms
Time between pulses: > 100 ms
Maximum voltage: 12 V
Maximum current: 10 mA
Isolation by optocoupler: 2.5 kV, 1 min.

SERIAL OUTPUT

Number of outputs: 1
Type: RS 485
Connection 2 or 4 wires
Baud rate (standard): 9600 bauds
Communication protocol: Modbus
Max. no. of devices per line: 32
Max. network length per line: 1250 m

AUXILIARY VOLTAGE

Aux. voltage: 100, 110, 230 or 400 VAC
Power consumption: 4 VA
Operating range: 80 -120% Un

Solicitar información

TTI-TTIM Energy meter

Ask information

TTI-TTIM Energy meter