TCIL2 Energy meter and network analyzer

The energy meter + network analyzer TCIL2 measures the parameters of a three-phase or single-phase low-voltage network. It has RS 485 communication and the capacity to connect up to 32 devices in the same grid or 128 through a transducer, being able to be controlled from any computer or networked device. Also available with Ethernet port. Up to 6 electric tariffs can be configured.

Connections

Dimensions

  • Bidirectional three phase energy meter
  • RS 485 and/or Ethernet communication. Modbus and Bacnet-IP protocol
  • Actrive energy counter resettable
  • Accuracy CL 0,5 active CL.2 reactive (EN 62053)
  • Indirect input (x/5 A or x/1A) programmable
  • Maximum demand
  • Maximum and minimum values
  • Pulse output: S0 (DIN 43864)
  • THD and harmonic up to 32
  • 4 rates in the TCIL2T version
  • LP (Energy Load Curve) or T memory (3 years of data with 17 programmable parameters)

VOLTAGE INPUT

  • Rated voltage (Un): 3 x 230 / 400 V AC
  • Burden per phase: < 3 W
  • Operating range: ± 20 % Un
  • Frequency: 50 – 60 Hz

CURRENT INPUT

  • IB intensity (IMAX): 1,5 (6) A
  • Own consumption: < 0,1 VA
  • Operating range: 0 – 100 % IMAX
    Starting current (In): 3 mA

TCIL2
TCIL2 TCP
TCIL2T
TCIL2T TCP
TCIL2 LP
TCIL2 LP TCP

Solicitar información