Phase Meters (Induction)

Power factor measurement, on single-phase or three-phase AC lines

Connections

Dimensions

AC SINGLE-PHASE / THREE-PHASE EQUILIBRATED 3 or 4 WIRES
Panel – 90º Scale
SC3V/ SC3VI – 96X96mm – 1,07kg
SC2V/ SC2VI – 144x144mm – 1,57kg

Panel – 360º Scale
SC3C/ SC3CI – 96X96mm – 1.10kg
SC2C/ SC2CI – 144x144mm – 1,60kg

THREE PHASE UNBALANCED 3-WIRE/ THREE PHASE UNBALANCED 4-WIRE
Panel – 90º scale
SC3VII/ SC3VIIn – 96x96mm – 1,40kg
SC2VII/ SC2VIIn – 144x144mm – 2,35kg

Panel – 360º Scale
SC3CII/ SC3CIIn – 96x96mm – 1,43kg
SC2CII/ SC2CIIn – 144x144mm – 2,38kg

Scale: CAP 0.5 – 1 – 0.5 IND or 0.8 – 1 0.2 IND (90º). CAP 0.1 – 1 – 0.1 IND 4 quadrants (360º)
– Accuracy: 1.5 % of 90º electrical
– Frequency: 50 or 60 Hz
– Voltage range: ±15 % Vn
– Voltage (Vn): 100, 110, 230, 400, 440 V
– Current range: 20-120%.
– Current input (In): 5A, 1A
– Burden: 20…30 mA (Voltage circuits)
– Burden: 1 VA (current circuits)