TA_PA Mini Split - Core Transformers
Mini transformer TA_PA open core transformer for measuring instrumentation. It is a through primary transformer for cable. It is notable for having ratios from 20A to 200A in the primary and with x/5A and x/1A output.
Mini transformer TA_PA open core transformer for measuring instrumentation. It is a through primary transformer for cable. It is notable for having ratios from 20A to 200A in the primary and with x/5A and x/1A output.
Technical details
- Technical characteristics
- Technical data
- Standards
Model/ Bar/ Cable
TA16PA / - / Ø16
TA20PA / - / Ø20
Safety data
- Continuous overload: 1.2 x In
- Rated short-circuit thermal I.: 60 x In or Ith limited by the cable or primary busbar dimensions.
- Nominal dynamic I.: 2.5 x Ith
- Operating voltage (maximum): 720 V AC
- Test voltage: 3 kV, 1 min.
- Frequency: 50 - 60 Hz
Additional information
- Working temperature: -5ºC to +40ºC.
- Storage temperature: -25ºC to +75ºC.
- Accuracy: 1 - 3
- Rated secondary I.: x/5A or x/1A
- Cable length: 1m
- EN 61869-1
- EN 61869-2
- EN 61000-6-3
- EN/IEC 6100-6-1