- Home
- Measuring Transducers
- Measuring Transducer ATIP ATUP
Measuring Transducer ATIP ATUP
Categories: Measuring Transducers
- User manual
- Certificate
Description: The ATIP ATUP measurement converter is controlled by a 16 bit microprocessor. Its configuration is done by means of software. It has 1 analog output and USB and RS485 serial port. Universal power supply 40V to 275 AC/DC.
- Technical features
- Technical data
- Versions
ANALOGUE OPUTPUT
- Programmable Zero, full scale and overange allowed.
- Insulated from input, power supply and RS485 serial port, but not from USB port.
SETTING
- MODBUS ID
- Baud rate, default 9600 bauds
- Primary current or primary voltage
- Secondary current or secondary voltage
SERIAL PORT
- USB and RS485. MODBUS/RTU protocol.
- RS485 isolated from signal input, power supply and analigue output.
- USB isolated from signal input and power supply but not from analogue output. It can be configured via USB without powering the equipment.
APPLICATION STANDARD
- IEC 60688 Electrical measuring transducers
- IEC 61010 Safety requirements
- IEC 61326 EMC requirements
- UL 94 Flammabillity
- IEC 60038 Standard voltages and current values
INPUT (SECONDARY RATED)
- ATIP: X/5 and X/1A
- ATUP: 230V and 110V. At the 110V input, other secondary values can be programmed, 57.7V; 63.5V; 100V…
- Measuring range: Up to 120%
ANALOGUE OUTPUT
- DC Current: .20mA and 0..5mA. Other output values under demand
- DC Voltage: 0..10V. Other output values under demand
- Load impedance: Ro (kΩ) = 127Io (mA) Max. for mA / Ro (kΩ) =Vo / 30 mA mín. for V
- Saturation limit: 120%
- Maximum open circuit voltage: 16V
- ATIP: Ripple ≤ 3 %
- ATUP: Ripple ≤ 0,3 %
- Response time: ≤ 200 ms (0 – 90 % lo)
AUXILIARY VOLTAGE
- 40..275V AC/DC, Burden: 1, 37..2,2 VA. 0,63..1W
No versions