Measuring Transducer ATIP ATUP

Description: The ATIP ATUP measurement converter is controlled by a 16 bit microprocessor. Its configuration is done by means of software. It has 1 analog output and USB and RS485 serial port. Universal power supply 40V to 275 AC/DC.

Connections

Dimensions

ANALOGUE OPUTPUT

  • Programmable Zero, full scale and overange allowed.
  • Insulated from input, power supply and RS485 serial port, but not from USB port.

SETTING

  • MODBUS ID
  • Baud rate, default 9600 bauds
  • Primary current or primary voltage
  • Secondary current or secondary voltage

SERIAL PORT

  • USB and RS485. MODBUS/RTU protocol.
  • RS485 isolated from signal input, power supply and analigue output.
  • USB isolated from signal input and power supply but not from analogue output. It can be configured via USB without powering the equipment.

APPLICATION STANDARD

  • IEC 60688 Electrical measuring transducers
  • IEC 61010 Safety requirements
  • IEC 61326 EMC requirements
  • UL 94 Flammabillity
  • IEC 60038 Standard voltages and current values

INPUT (SECONDARY RATED)

  • ATIP: X/5 and X/1A
  • ATUP: 230V and 110V. At the 110V input, other secondary values can be programmed, 57.7V; 63.5V; 100V…
  • Measuring range: Up to 120%

ANALOGUE OUTPUT

  • DC Current: .20mA and 0..5mA. Other output values under demand
  • DC Voltage: 0..10V. Other output values under demand
  • Load impedance: Ro (kΩ) = 127Io (mA) Max. for mA / Ro (kΩ) =Vo / 30 mA mín. for V
  • Saturation limit: 120%
  • Maximum open circuit voltage: 16V
  • ATIP: Ripple ≤ 3 %
  • ATUP: Ripple ≤ 0,3 %
  • Response time: ≤ 200 ms (0 – 90 % lo)

AUXILIARY VOLTAGE

  • 40..275V AC/DC, Burden: 1, 37..2,2 VA. 0,63..1W