Programmable Multiple Indicators (CA) DMP3

The DMP3 multiple indicator is a meter with voltage and current inputs designed to display the FREQUENCY, CURRENTS and VOLTAGES of a three-phase network, with or without neutral, by connection to current transformers. It allows the simultaneous display of three currents, a selectable voltage and the frequency.

The DMP3 multiple indicator is a meter with voltage and current inputs designed to display the FREQUENCY, CURRENTS and VOLTAGES of a three-phase network, with or without neutral, by connection to current transformers. It allows the simultaneous display of three currents, a selectable voltage and the frequency.


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Technical characteristics
    • Technical data

    3 currents, 3 phase-to-phase voltages, 3 phase-to-neutral voltages, frequency.
    Current and voltage isolated.
    96x96mm - 0,5kg
    Transformer ratios: 1, 5, 10, 15, 15, 20, 25, 25, 30, 40, 40, 50,70, 75, 80, 90, 100, 120, 125, 150, 160, 160, 200, 250, 300, 400, 500, 600, 700, 750, 750, 800, 900, 1000,1200, 1250, 1400, 1500, 1600, 1750, 1800, 2000, 2200, 2250, 2400, 2500, 2750, 3000, 3500, 4000, 5000, 5500, 6000, 6500, 7000, 7500, 8000, 9000 A

    Voltage: Max. 300 V phase-to-neutral // Max. 300 V phase-to-neutral. 500 V phase-phase
    Load: <1 VA
    Frequency: 10-100Hz
    Current: x/5 (programmable)
    Load: <0.5A
    Accuracy: 0.5% FE + 2 digits
    Power supply: 230VAC ± 20%
    Consumption: <5VA
    Measurement refresh: 3 times per second (approx.)
    Terminals: Unpluggable with 2.5 mm² cable capacity