TCIL2TLP Energy meter

The TCIL2TLP is indirect three-phase meter & analyzer. It acts as an energy meter and measures the parameters of a low voltage three phase ir single-phase network such as: voltage, current active power, reactive power, apparent, power factor, frequency and maximum demand in low voltage. It has a RS 485 and Ethernet port (TCP model). 6 tariffs available. Load curve available.
  • Three-phase or single-phase consumption
  • Current
  • Voltage (Phase-phase and phase-neutral)
  • Frequency
  • Power factor
  • Energy (Imported and exported). Measure in all 4 quadrants
  • Active and reactive power (per phase and total)
  • Power quality analysis (THD V and I, harmonics up to 31, maximum demand I, P, Q, S)
  • Modbus or Bacnet communications (programmable)
  • Load curve available

Connections

Dimensions

  • VOLTAGE INPUT
    • Rated voltage (Un): 3 x 230 / 400 V AC
    • Voltage measurement range:  63 to 276 Vpn AC
    • Frequency: 50 – 60 Hz
    • Network type: 1P2W, 3P3W to 3P4W

    CURRENT INPUT

    • Base current: 1,5 (6) A
    • Rated current: /5 or /1 programmable
    • Maximum current: 2 In
    • Current measuring range: 0 – 120 % In
    • Starting current: 3 mA
    • Maximum burden: < 0,1 VA
    • Contunuous overload: 2 In
    • Instant overload: 10 In 5 s
    • Transmission speed: 1200 – 19200 bps
    • Material: ABS, UL94 V0

    POWER SUPPLY

    • Auxiliary voltage: Self supplied
    • Auxiliary voltage consumption: < 0,6 Va per phase

Solicitar información

TCIL2TLP Energy meter

Ask information

TCIL2TLP Energy meter