M1DL1 MID Energy meter

The accountant M1DL1-MID single-phase direct is also an analyser, measuring the various parameters of a single-phase low-voltage network. In addition, it has MID certification for active energy, it is not bidirectional. The measured values can be displayed on the built-in display.

Description: The accountant M1DL1-MID single-phase direct is also an analyser, measuring the various parameters of a single-phase low-voltage network. In addition, it has MID certification for active energy, it is not bidirectional. The measured values can be displayed on the built-in display.

 


    BASIC DATA PROTECTION INFORMATION: Data controller: SOCIEDAD ANÓNIMA DE CONSTRUCCIONES INDUSTRIALES Purpose of processing: To manage the queries made and to send newsletters, commercial communications and promotions. Legitimisation of the processing: Legitimate interest and consent of the data subject. Retention of data: Data will be kept for as long as there is a mutual interest or for the time necessary to comply with legal obligations. Recipients: Service providers or collaborators. Rights: Right to withdraw consent at any time. Right of access, rectification, portability and deletion of your data and the right to limit or oppose its processing. Contact details for exercising your rights: info@saci.es Additional information: You can consult additional information in our Privacy Policy.

    Technical details

    • Connections
    • Technical characteristics
    • Technical data

    Accuracy

    • Active energy: Class B
    • Active power: Class 0.5
    • Power factor: Class 0.5
    • Current: Class 0.5
    • Voltage: Class 0.5

    Features

    • Auxiliary voltage: Self-powered
    • Housing material: PBT, PC
    • Mounting type: DIN rail
    • Display type: LCD
    • Resolution: 5 digits + 2 decimals
    • Digital outputs: Verification LED 1000 Imp/kWh
    • Pulse outputs: SO 1000 imp/kWh
    • Type of terminals: screw

    Standards

    • EN 50470-1
    • EN 50470-3
    • ENG 2053-23
    • DIN 43864
    • EN 61010

    Entrance

    • Rated voltage (Un): 230 V AC
    • Voltage measuring range: 230 V ± 20 %
    • Rated current: 0.25 - (50) A
    • Current measuring range: 0 - 100% IMAX
    • Starting current: 20 mA
    • Frequency: 50 Hz
    • Network type: 1P2W
    • Self consumption: < 8 VA, < 0.4W

    Environment

    • Degree of protection: IP51
    • Electromagnetic environment: E2
    • Mechanical environment: M1
    • Average relative humidity: ≤ 75%
    • Maximum relative humidity: ≤ 95% without condensation
    • Operating temperature: - 25 / + 55 ºC
    • Storage temperature: -25 / + 70 ºC
    • Weight: 0.1 Kg