ANG96 Network analyzer

Categories:
Description: The ANG96 network analyzer ir a digital device, able to measurement all the variables associated with an electrical line. It accepts the three currents and three voltage signal in a four-wire configuration. It is also possible to use it in a three-wire configuration, using two or three current transformers.

The ANG96 has an optional TCP/IP protocol in a RJ45 connector for a LLAN network. The device only needs to be configurated with its own IP, the Netmask, the gateway and a free TCP port to communicate with any internal or external equipment.

Connections

Dimensions

  • DIN size 96 x 96
  • LCD 128 x 64 display with backlight
  • 4 cuadrant measurement
  • Neutral current measurement
  • Harmonic distortion (THD on V and I)
  • Maximum demand (A, kw, kVA, and kvar)
  • Maximum and minimum values
  • True RMS voltage and current
  • Serial port RS 485
  • 2 hour counters
  • TCP/IP (optional: ANG-TCP)
  • 4 hours counters (optional: ANG96-G)

INPUT

  • Rated voltage (Un): 0 – 520 V AC
  • Burden: < 1 mA per phase
  • Rated current (In): 1 and 5 A
  • Burden: < 0,3 VA per phase
  • Operating range: 10 – 120% In
  • Frequency: 45 – 65 Hz
  • Overload: 2 In permanent, 20 In 1 s // 1,2 Vn permanent, 2 Vn 10 s

AUXILIARY VOLTAGE

  • Universal Aux. V: 85 / 264 C AV; 80 / 300 V DC
  • Burden: < 4 VA

OUTPUT

  • Relays: 250 V AC 3A
  • Pulse weight: 60 ms
  • Serial port: RS 485
  • Protocol: Modbus RTU
  • Baud rate: Programmable 1200 – 19200 bps // standard 9600 bps
  • Connection: 2 wires

Unique model

Solicitar información

ANG96 Network analyzer

Ask information

ANG96 Network analyzer