- Home
- Network Analyzer
- AHM3 Network analyzer
AHM3 Network analyzer
Categories: Network Analyzer
- Certificate
Description: The network analyzer AHM3 is designed to be used for the measurement and calculation of electrical variables, such as voltage, current, frequency, power, power factor, energy, harminic components, etc. in low, medium and high voltage power distribution.
The AHM3 it is capable of single-phase, two-phase, or three-phase measurement ad can be used it two-wire, three-wire- four-wire. TN, TT andIT systems. There are four interfaces on the meter for modules which are used to extend functions.
AHM3-SMTP version
Remote data reading and configuration via web. Alarm sending configuration via e-mail. Reading of up to 16 tariffs, calculation of the CO2 carbon footprint and detail of costs per serial line.
Control the consumption and quality of your installation’s network from any location. Store up to 16 recent events on the web and download the data to Excel.
Receive the events you want by email: up to 3 email addresses simultaneously.
- Technical features
- Technical data
- Versions
- DIN 96×96 mm
- 13 additional modules
- 4 interfaces for modules
- THD on V and I
- Harmonic RMS (1-63)
- Maximum demand, A, kW, kVA, kvar
- Maximum and minimum values
- Programmable rated V and I
- 4 quadrant measurement
- waveform
INPUT
- Rated voltage (Un): 3 x 400 / 690 V AC
- Overload: 1,2 Un
- Impedance > 1 MΩ
- Rated current (In): 1 A and 5 A
- Overload continuous: 10 In / 5s or 20 In / 1s
- Burden: < 0,1 VA
- Rated value: < 20 mΩ
AUXILIARY VOLTAGE
- Aux. V AC / DC: 80 – 270 V
- Burden: < 10 VA
OUTPUT
- Relay output: 250V /5A AC; 30 V /5A DC
- Isolation: 2500 V AC
- Energy pulse width: 80 ± 20 % ms
- RS485 port: Modbus-RTU
- Baud rate: Up to 38400 bps programmable
- AHM3 – Basic Version
- AHM3-RC – Rogowski Version
- AHM3-SMTP – Web server Versión