AHM3 Network analyzer

Categories:
Description: The network analyzer AHM3 is designed to be used for the measurement and calculation of electrical variables, such as voltage, current, frequency, power, power factor, energy, harminic components, etc. in low, medium and high voltage power distribution. The AHM3 it is capable of single-phase, two-phase, or three-phase measurement ad can be used it two-wire, three-wire- four-wire. TN, TT andIT systems. There are four interfaces on the meter for modules which are used to extend functions.

AHM3-SMTP version

Remote data reading and configuration via web. Alarm sending configuration via e-mail. Reading of up to 16 tariffs, calculation of the CO2 carbon footprint and detail of costs per serial line.

Control the consumption and quality of your installation’s network from any location. Store up to 16 recent events on the web and download the data to Excel.

Receive the events you want by email: up to 3 email addresses simultaneously.

Connections

Dimensions

  • DIN 96×96 mm
  • 13 additional modules
  • 4 interfaces for modules
  • THD on V and I
  • Harmonic RMS (1-63)
  • Maximum demand, A, kW, kVA, kvar
  • Maximum and minimum values
  • Programmable rated V and I
  • 4 quadrant measurement
  • waveform

INPUT

  • Rated voltage (Un): 3 x 400 / 690 V AC
  • Overload: 1,2 Un
  • Impedance > 1 MΩ
  • Rated current (In): 1 A and 5 A
  • Overload continuous: 10 In / 5s or 20 In / 1s
  • Burden: < 0,1 VA
  • Rated value: < 20 mΩ

AUXILIARY VOLTAGE

  • Aux. V AC / DC: 80 – 270 V
  • Burden: < 10 VA

OUTPUT

  • Relay output: 250V /5A AC; 30 V /5A DC
  • Isolation: 2500 V AC
  • Energy pulse width: 80 ± 20 % ms
  • RS485 port: Modbus-RTU
  • Baud rate: Up to 38400 bps programmable
  • AHM3 – Basic Version
  • AHM3-RC – Rogowski Version
  • AHM3-SMTP – Web server Versión

Solicitar información

AHM3 Network analyzer

Ask information

AHM3 Network analyzer